Naslov Optimizacija sustava grijanja i hlađenja hotela
Naslov (engleski) The optimization of heating and cooling system for the hotel
Autor Roman Čataj
Mentor Igor Balen (mentor)
Ustanova koja je dodijelila akademski / stručni stupanj Sveučilište u Zagrebu Fakultet strojarstva i brodogradnje Zagreb
Datum i država obrane 2020-07-14, Hrvatska
Znanstveno / umjetničko područje, polje i grana TEHNIČKE ZNANOSTI Strojarstvo Procesno energetsko strojarstvo
Sažetak U ovom radu uspoređeno je nekoliko tehničkih rješenja sustava grijanja, hlađenja i pripreme potrošne tople vode za referentnu niskoenergetsku hotelsku zgradu u primorskoj Hrvatskoj prema kriteriju primarne energije, troškova investicije i troškova pogona. Referentna hotelska zgrada se sastoji od 7 etaža i ukupne je podne površine 6.912 m2, potrebnog ogrjevnog učina 260 kW i rashladnog učina 400 kW.
Zgrada je podijeljena u tri proračunske zone. Zona broj 1 su sobe, nalazi se na katovima od 2 do
... Više 6, prirodno je ventilirana i ima cirkulacijsku petlju potrošne tople vode. Zona broj 2 je kuhinja, nalazi se na prvom katu, ima mehaničku ventilaciju s rekuperatorima i nema cirkulacijsku petlju potrošne tople vode. Zona broj 3 su zajedničke prostorije, nalazi se u prizemlju i na prvom katu, ima mehaničku ventilaciju s rekuperatorima i nema cirkulacijsku petlju potrošne tople vode.
Za sve proračunske zone je predviđeni sustav grijanja i hlađenja pomoću ventilokonvektora u dvocijevnoj izvedbi. Za sve proračunske zone je temperaturni režim grijanja je 45/40°C, a hlađenja 7/12°C. Potrebna toplinska energija za grijanje zgrade QH,nd i za hlađenje zgrade QC,nd izračunata je prema HRN EN ISO 13790 mjesečnom i jednostavnom satnom metodom za karakterističan dan u mjesecu te su rezultati međusobno uspoređeni. Proračun sustava za pripremu PTV-a je prema normama HRN EN 15316-3-1, HRN EN 15316-3-2, HRN EN 15316-3-3. Proračun sustava za grijanje i hlađenje prostora je prema normama HRN EN 15316-2-1, HRN EN 15316-2-3, HRN EN 15316-4-7, HRN EN 15316-4-2.
U ovom radu uspoređena su sljedeća tehnička rješenja sustava grijanja, hlađenja i pripreme potrošne tople vode:
1. Dizalica topline zrak-voda s rekuperacijom i booster dizalica topline voda-voda
2. Dizalica topline voda-voda s rekuperacijom i booster dizalica topline voda-voda
3. Dizalica topline voda-voda bez rekuperacije i booster dizalica topline voda-voda
4. Kotao na drvenu sječku, rashladnik zrak-voda i booster dizalica topline voda-voda
5. Kotao na drvenu sječku i rashladnik zrak-voda
Booster dizalica topline služi za pripremu potrošne tople vode temperature 60°C.
Za svako tehničko rješenje priložena je shema spajanja sustava.
Financijski najpovoljnije rješenje te s najmanjim utroškom primarne energije i emisijom CO2 je tehničko rješenje broj 5. Najskuplje i s većim utroškom primarne energije te s većom emisijom CO2 je tehničko rješenje broj 1. Usporedbom ukupnih troškova nakon perioda od 15 godina, tehničko rješenje broj 1 je 26% skuplje od tehničkog rješenja broj 5. Sakrij dio sažetka
Sažetak (engleski) Within this thesis, several technical solutions for heating, cooling and preparation of domestic hot water systems were compared for a reference low-energy hotel building, based on criteria of primary energy, investment costs and operating costs. The reference hotel building is located in Primorska Hrvatska (Coastal Croatia) and has seven levels. The total floor area is 6.912 m2 and the needed generator's heating capacity is a minimum of 260 kW while the cooling capacity is 400 kW.
The
... Više building is divided into three zones. Zone number 1, rooms, is located on floors from 2 to 6. Zone number 1 is naturally ventilated and has a circulation loop for DHW. Zone number 2, kitchen, is on the first floor. Zone number 2 is mechanically ventilated and has no circulation loop for DHW. Zone number 3, common areas, is located on the ground level and on the first floor. Zone number 3 is mechanically ventilated and has no circulation loop for DHW. Envisaged heating/cooling system is two pipe with fan coils. Heating regime is 45/40°C while the cooling regime is 7/12°C. Energy need for heating QH,nd and energy need for cooling QC,nd were calculated according to HRN EN ISO 13790 using both monthly method and simple hourly method and results of both methods were compared.
Following technical solutions for heating, cooling and DHW systems were compared:
1. Air-to-water heat pump with condenser heat recovery and booster heat pump water-to-water
2. Water-to-water heat pump with condenser heat recovery and booster heat pump water-to-water
3. Water-to-water heat pump without condenser heat recovery and booster heat pump water-to-water
4. Biomass boiler, air-to-water chiller and booster heat pump water-to-water
5. Biomass boiler and air-to-water chiller
Booster heat pump is used for the preparation of 60°C domestic hot water.
An assembly diagram is provided for each technical solution.
The most expensive and with a big usage of primary energy and CO2 emission was technical solution number 1. The least expensive and with the lowest usage of primary energy and CO2 emission was technical solution number 5. Sakrij dio sažetka
Ključne riječi
grijanje
hlađenje
PTV
dizalica topline zrak-voda
dizalica topline voda-voda
kotao na biomasu
rashladnik zrak-voda
jednostavna satna metoda
mjesečna metoda
Ključne riječi (engleski)
heating
cooling
DHW
air-to-water heat pump
water-to-water heat pump
air-to-water chiller
biomass boiler
monthly method
simple hourly method
Jezik hrvatski
URN:NBN urn:nbn:hr:235:895547
Studijski program Naziv: Strojarstvo Vrsta studija: sveučilišni Stupanj studija: diplomski Akademski / stručni naziv: magistar/magistra inženjer/inženjerka strojarstva (mag. ing. mech.)
Vrsta resursa Tekst
Način izrade datoteke Izvorno digitalna
Prava pristupa Otvoreni pristup
Uvjeti korištenja
Datum i vrijeme pohrane 2020-07-07 09:41:20